N2XS2Y

PE medium voltage cable with copper conductor

N2XS2Y, VDE, PE medium voltage cable acc. VDE 0276-620, with copper conductor, for fixed installation

  • 3 voltage classes: 6/10 (12) kV, 12/20 (24) kV, 18/30 (36) kV
  • With copper conductor

Suitable for outdoor useMechanical resistanceUV-resistant

VDE

Article number Number of cores and mm² per conductorOuter diameter [mm]Copper index (kg/km)Weight (kg/km)
6/10 (12) kV
38107786
1x35 RM/1624518770
38001000
1X50 RM/1625662900
1552070
1X70 RM/16268541123
38107787
1x70 RM/502712381450
38107788
1x95 RM/162810941384
38107789
1x120 RM/163013341623
38107029
1X150 RM/253117231966
38107790
1x185 RM/253320592335
1550067
1X240 RM/253525872885
38107791
1x300 RM/253731633480
38107792
1x400 RM/354142344381
38107793
1x500 RM/354351945382
12/20 (24) kV
1552068
1X35 RM/1628518914
1552069
1X50 RM/16296621049
1552041
1X70 RM/16318541289
3828017
1X95 RM/163210941554
38107794
1x120 RM/163413341802
1552047
1X150 RM/253517232153
38107795
1x185 RM/253720592533
38107796
1x240 RM/253925873096
38107797
1x300 RM/254231633705
38107798
1x300 RM/354232743800
38107799
1x400 RM/354442344519
38107800
1x500 RM/354751945647
38107801
1x630 RM/355164427049
18/30 (36) kV
3036224
1X50 RM/16346621260
38107802
1x70 RM/16368541656
38107803
1x95 RM/163710941789
38107804
1x120 RM/163913342048
38107805
1x150 RM/254017232409
3028167
1X185 RM/254220592802
38107806
1x240 RM/254425873382
38107807
1x300 RM/254731634009
38107808
1x400 RM/355042344934
38107809
1x500 RM/355351946009
38107810
1x630 RM/355664427423

Application range

  • Power and control cable for fixed installation in the following applications:
  • In water, in ground, outdoors and indoors
  • In cable trays for power stations, industry, and distribution networks
  • Burial without additional, suitable underground protection according to HD 620/VDE 0276-620 - Part 10-C (point 4): normal minimum installation depth 0.6 m, but at least 0.8 m under roads

Product features

  • Suitable for installation or operation under high mechanical stress due to the PE-sheath
  • Current rating according to HD 620/VDE 0276-620, Part 10-C, Table 7 (buried at +20 °C ground temperature according to HD 620/VDE 0276-620, Part 10-C, point 5) for routing underground and Table 8 (in the air at an air temperature of +30 °C according to HD 620/VDE 0276-620, Part 10-C, point 5) when used outdoors; but always taking into consideration corrections/reductions to the current rating that may be necessary according to VDE 0298-4, and VDE 0298-4 (also refer to the catalogue appendix T12) for installation in and on buildings

Norm references / Approvals

  • HD 620/ VDE 0276-620

Product Make-up

  • Copper conductor
  • Abbreviation "rm":
    r = round conductor form;
    m = multi-wire conductor
  • Core insulation: Cross-linked Polyethylen (XLPE)
  • Screen made of copper wires with one or two copper bond counter spiral
  • Outer sheath: PE, black

Classification ETIM 5

  • ETIM 5.0 Class-ID: EC001140
  • ETIM 5.0 Class-Description: Medium voltage power cable

Classification ETIM 6

  • ETIM 6.0 Class-ID: EC001140
  • ETIM 6.0 Class-Description: Medium voltage power cable

Conductor stranding

  • Multi-wire

Minimum bending radius

  • Fixed installation: 15 x outer diameter

Nominal voltage

  • U0/U: 6/10 (12) kV, 12/20 (24) kV, 18/30 (36) kV

Test voltage

  • Depending on nominal voltage:
    6/10 kV: 15 kV
    12/20 kV: 30 kV
    18/30 kV: 45 kV

Temperature range

  • During installation: -40°C to +70°C
  • Fixed installation: -40°C to +90°C

  • Unless specified otherwise, the shown product values are nominal values. Detailed values (e.g. tolerances) are available upon request.
  • Aluminium price basis: excludes aluminium. Refer to catalogue appendix T17 for the application and definition of "Metal price basis" and "Metal index".
  • Please find our standard lengths at: www.lappkabel.de/en/cable-standardlengths
  • * Trade product, no Lapp product
  • Photographs and graphics are not to scale and do not represent detailed images of the respective products.