NA2XSY

PVC medium voltage cable with aluminium conductor

NA2XSY, VDE, PVC medium voltage cable acc. VDE 0276-620, with aluminium conductor, for fixed installation

  • 3 voltage classes: 6/10 kV, 12/20 kV, 18/30 kV
  • With aluminium conductor

VDE

Article number Number of cores and mm² per conductor Copper index (kg/km) Alu index (kg/km) Outer diameter [mm] Weight (kg/km)
6/10 kV
38107855
1x50 RM/16 182 145 25 719
38107856
1x70 RM/16 182 203 26 810
38107857
1x70 RM/35 394 203 27 1000
38107858
1x95 RM/16 182 276 28 921
38107859
1x120 RM/16 182 348 30 1022
38107860
1x150 RM/25 283 435 31 1209
38107861
1x185 RM/25 283 537 33 1351
38107862
1x240 RM/25 283 696 35 1561
38107863
1x300 RM/25 283 870 37 1771
3038844
1X400 RM/35 394 1160 40 2184
38107864
1x500 RM/35 394 1450 43 2517
12/20 kV
38107865
1x50 RM/16 182 145 29 889
38107866
1x70 RM/16 182 203 31 988
38107867
1x95 RM/16 182 276 32 1109
38107868
1x120 RM/16 182 348 34 1220
38107869
1x150 RM/25 283 435 35 1414
38802239
1X185 RM/25 283 537 37 1567
38107870
1x240 RM/25 283 696 39 1791
38107871
1x300 RM/25 283 870 41 2014
38107872
1x400 RM/35 394 1160 44 2412
38107873
1x500 RM/35 394 1450 47 2798
18/30 kV
38107874
1x50 RM/16 182 145 34 1124
38107875
1x70 RM/16 182 303 36 1234
38107876
1x70 RM/25 283 203 36 1300
38107877
1x95 RM/16 182 276 37 1367
38107878
1x120 RM/16 182 348 39 1488
38107879
1x150 RM/25 283 435 40 1692
38107880
1x185 RM/25 283 537 42 1858
38107881
1x240 RM/25 283 696 44 2099
38107882
1x300 RM/25 283 870 46 2339
38107883
1x400 RM/35 394 1160 49 2758
38107884
1x500 RM/35 394 1450 52 3189
38107885
1x630 RM/35 394 1827 56 3724

Application range

  • Power and control cable for fixed installation in the following applications:
  • In water, in ground, outdoors and indoors
  • In cable trays for power stations, industry, and distribution networks
  • Burial without additional, suitable underground protection according to HD 620/VDE 0276-620 - Part 10-C (point 4): normal minimum installation depth 0.6 m, but at least 0.8 m under roads

Product features

  • Flame-retardant according IEC 60332-1-2
  • Current rating according to HD 620/VDE 0276-620, Part 10-C, Table 7 (buried at +20 °C ground temperature according to HD 620/VDE 0276-620, Part 10-C, point 5) for routing underground and Table 8 (in the air at an air temperature of +30 °C according to HD 620/VDE 0276-620, Part 10-C, point 5) when used outdoors; but always taking into consideration corrections/reductions to the current rating that may be necessary according to VDE 0298-4, and VDE 0298-4 (also refer to the catalogue appendix T12) for installation in and on buildings

Norm references / Approvals

  • HD 620/ VDE 0276-620

Product Make-up

  • Aluminium conductor
  • Abbreviation "rm":
    r = round conductor form;
    m = multi-wire conductor
  • Core insulation: Cross-linked Polyethylen (XLPE)
  • Screen made of copper wires with one or two copper bond counter spiral
  • Outer sheath: PVC, red

Classification ETIM 5

  • ETIM 5.0 Class-ID: EC001140
  • ETIM 5.0 Class-Description: Medium voltage power cable

Classification ETIM 6

  • ETIM 6.0 Class-ID: EC001140
  • ETIM 6.0 Class-Description: Medium voltage power cable

Conductor stranding

  • Multi-wire

Minimum bending radius

  • Fixed installation: 15 x outer diameter

Nominal voltage

  • U0/U: 6/10 kV, 12/20 kV, 18/30 kV

Test voltage

  • Depending on nominal voltage:
    6/10 kV: 15 kV
    12/20 kV: 30 kV
    18/30 kV: 45 kV

Temperature range

  • During installation: -5°C to +50°C
  • Fixed installation: -40°C to +90°C

  • Unless specified otherwise, the shown product values are nominal values. Detailed values (e.g. tolerances) are available upon request.
  • Aluminium price basis: excludes aluminium. Refer to catalogue appendix T17 for the application and definition of "Metal price basis" and "Metal index".
  • Please find our standard lengths at: www.lappkabel.de/en/cable-standardlengths
  • Photographs and graphics are not to scale and do not represent detailed images of the respective products.