NA2XSY

PVC medium voltage cable with aluminium conductor

NA2XSY, VDE, PVC medium voltage cable acc. VDE 0276-620, with aluminium conductor, for fixed installation

  • 3 voltage classes: 6/10 (12) kV, 12/20 (24) kV, 18/30 (36) kV
  • With aluminium conductor

VDE

Article number Number of cores and mm² per conductorOuter diameter [mm]Copper index (kg/km)Weight (kg/km)
6/10 (12) kV
38107855
1x50 RM/1625182719
38107856
1x70 RM/1626182810
38107857
1x70 RM/35273941000
38107858
1x95 RM/1628182921
38107859
1x120 RM/16301821022
38107860
1x150 RM/25312831209
38107861
1x185 RM/25332831351
38107862
1x240 RM/25352831561
38107863
1x300 RM/25372831771
3038844
1X400 RM/35403942184
38107864
1x500 RM/35433942517
12/20 (24) kV
38107865
1x50 RM/1629182889
38107866
1x70 RM/1631182988
38107867
1x95 RM/16321821109
38107868
1x120 RM/16341821220
38107869
1x150 RM/25352831414
38802239
1X185 RM/25372831567
38107870
1x240 RM/25392831791
38107871
1x300 RM/25412832014
38107872
1x400 RM/35443942412
38107873
1x500 RM/35473942798
18/30 (36) kV
38107874
1x50 RM/16341821124
38107875
1x70 RM/16361821234
38107876
1x70 RM/25362831300
38107877
1x95 RM/16371821367
38107878
1x120 RM/16391821488
38107879
1x150 RM/25402831692
38107880
1x185 RM/25422831858
38107881
1x240 RM/25442832099
38107882
1x300 RM/25462832339
38107883
1x400 RM/35493942758
38107884
1x500 RM/35523943189
38107885
1x630 RM/35563943724

Application range

  • Power and control cable for fixed installation in the following applications:
  • In water, in ground, outdoors and indoors
  • In cable trays for power stations, industry, and distribution networks
  • Burial without additional, suitable underground protection according to HD 620/VDE 0276-620 - Part 10-C (point 4): normal minimum installation depth 0.6 m, but at least 0.8 m under roads

Product features

  • Flame-retardant according IEC 60332-1-2
  • Current rating according to HD 620/VDE 0276-620, Part 10-C, Table 7 (buried at +20 °C ground temperature according to HD 620/VDE 0276-620, Part 10-C, point 5) for routing underground and Table 8 (in the air at an air temperature of +30 °C according to HD 620/VDE 0276-620, Part 10-C, point 5) when used outdoors; but always taking into consideration corrections/reductions to the current rating that may be necessary according to VDE 0298-4, and VDE 0298-4 (also refer to the catalogue appendix T12) for installation in and on buildings

Norm references / Approvals

  • HD 620/ VDE 0276-620

Product Make-up

  • Aluminium conductor
  • Abbreviation "rm":
    r = round conductor form;
    m = multi-wire conductor
  • Core insulation: Cross-linked Polyethylen (XLPE)
  • Screen made of copper wires with one or two copper bond counter spiral
  • Outer sheath: PVC, red

Classification ETIM 5

  • ETIM 5.0 Class-ID: EC001140
  • ETIM 5.0 Class-Description: Medium voltage power cable

Classification ETIM 6

  • ETIM 6.0 Class-ID: EC001140
  • ETIM 6.0 Class-Description: Medium voltage power cable

Conductor stranding

  • Multi-wire

Minimum bending radius

  • Fixed installation: 15 x outer diameter

Nominal voltage

  • U0/U: 6/10 (12) kV, 12/20 (24) kV, 18/30 (36) kV

Test voltage

  • Depending on nominal voltage:
    6/10 kV: 15 kV
    12/20 kV: 30 kV
    18/30 kV: 45 kV

Temperature range

  • During installation: -5°C to +50°C
  • Fixed installation: -40°C to +90°C

  • Unless specified otherwise, the shown product values are nominal values. Detailed values (e.g. tolerances) are available upon request.
  • Aluminium price basis: excludes aluminium. Refer to catalogue appendix T17 for the application and definition of "Metal price basis" and "Metal index".
  • Please find our standard lengths at: www.lappkabel.de/en/cable-standardlengths
  • * Trade product, no Lapp product
  • Photographs and graphics are not to scale and do not represent detailed images of the respective products.