N2XSY

PVC medium voltage cable with copper conductor

N2XSY, VDE, PVC medium voltage cable acc. VDE 0276-620, with copper conductor, for fixed installation

  • 3 voltage classes: 6/10 (12) kV, 12/20 (24) kV, 18/30 (36) kV
  • With copper conductor

VDE

Article number Number of cores and mm² per conductorOuter diameter [mm]Copper index (kg/km)Weight (kg/km)
6/10 (12) kV
3037523
1X35 RM/1624518867
3022192
1X50 RM/16256621001
38007455
1X70 RM/16268541232
3037524
1X95 RM/162810941500
38101056
1X120 RM/163013341746
1550537
1X150 RM/253117232095
38007456
1X185 RM/253320592472
1550538
1X240 RM/253525873032
38100269
1X300 RM/253731633637
38101815
1X400 RM/354042344535
38101814
1X500 RM/354351945566
38107775
1x630 RM/354764426935
12/20 (24) kV
1552067
1X35 RM/16285181030
1552040
1X50 RM/16296621169
38300006
1X70 RM/16318541410
3801425
1X95 RM/163210941689
38100617
1X120 RM/163413341944
1550554
1X150 RM/253517232301
38107776
1x185 RM/253720592689
38300015
1X240 RM/253925873262
38300017
1X300 RM/254231633882
38101817
1X400 RM/354442344797
38101816
1X500 RM/354751945850
38107777
1x630 RM/355164427237
38107778
1x800 RM/355680749058
18/30 (36) kV
38107779
1x35 RM/1624518770
38300014
1X50 RM/16346621403
38107780
1x70 RM/16368541656
38801995
1X95 RM/163710941947
38300009
1X120 RM/163913342213
38107781
1x150 RM/254017232580
38107782
1x185 RM/254220592980
38106711
1X240 RM/254425873570
38107783
1x300 RM/254731634208
38107784
1x400 RM/355042345147
38107785
1x500 RM/355351946244

Application range

  • Power and control cable for fixed installation in the following applications:
  • In water, in ground, outdoors and indoors
  • In cable trays for power stations, industry, and distribution networks
  • Burial without additional, suitable underground protection according to HD 620/VDE 0276-620 - Part 10-C (point 4): normal minimum installation depth 0.6 m, but at least 0.8 m under roads

Product features

  • Flame-retardant according IEC 60332-1-2
  • Current rating according to HD 620/VDE 0276-620, Part 10-C, Table 7 (buried at +20 °C ground temperature according to HD 620/VDE 0276-620, Part 10-C, point 5) for routing underground and Table 8 (in the air at an air temperature of +30 °C according to HD 620/VDE 0276-620, Part 10-C, point 5) when used outdoors; but always taking into consideration corrections/reductions to the current rating that may be necessary according to VDE 0298-4, and VDE 0298-4 (also refer to the catalogue appendix T12) for installation in and on buildings

Norm references / Approvals

  • HD 620/ VDE 0276-620

Product Make-up

  • Copper conductor
  • Abbreviation "rm":
    r = round conductor form;
    m = multi-wire conductor
  • Core insulation: Cross-linked Polyethylen (XLPE)
  • Screen made of copper wires with one or two copper bond counter spiral
  • Outer sheath: PVC, red

Classification ETIM 5

  • ETIM 5.0 Class-ID: EC001140
  • ETIM 5.0 Class-Description: Medium voltage power cable

Classification ETIM 6

  • ETIM 6.0 Class-ID: EC001140
  • ETIM 6.0 Class-Description: Medium voltage power cable

Conductor stranding

  • Multi-wire

Minimum bending radius

  • Fixed installation: 15 x outer diameter

Nominal voltage

  • U0/U: 6/10 (12) kV, 12/20 (24) kV, 18/30 (36) kV

Test voltage

  • Depending on nominal voltage:
    6/10 kV: 15 kV
    12/20 kV: 30 kV
    18/30 kV: 45 kV

Temperature range

  • During installation: -5°C to +50°C
  • Fixed installation: -40°C to +90°C

  • Unless specified otherwise, the shown product values are nominal values. Detailed values (e.g. tolerances) are available upon request.
  • Aluminium price basis: excludes aluminium. Refer to catalogue appendix T17 for the application and definition of "Metal price basis" and "Metal index".
  • Please find our standard lengths at: www.lappkabel.de/en/cable-standardlengths
  • * Trade product, no Lapp product
  • Photographs and graphics are not to scale and do not represent detailed images of the respective products.