ÖLFLEX® CLASSIC 135 CH

Screened halogen-free control cable with improved fire characteristics

ÖLFLEX® CLASSIC 135 CH -halogen-free control cable, HFFR, flexible and screened for various applications, U0/U: 300/500V

  • CPR: Article number choice under www.lappkabel.com/cpr
  • For use within public buildings and industrial plants
  • A temporary outdoor use is possible

Flame-retardantHalogen-freeInterference signals

CERUDNVEACFire

Article number Number of cores and mm² per conductorOuter diameter [mm]Copper index (kg/km)Weight (kg/km)
ÖLFLEX® CLASSIC 135 CH
1123200
2 X 0.55.93651
1123201
3 G 0.56.24361
1123202
3 X 0.56.24361
1123203
4 G 0.56.64972
1123204
4 X 0.56.64972
1123205
5 G 0.57.15785
1123206
5 X 0.57.15785
1123208
7 G 0.57.769103
1123209
7 X 0.57.769103
1123213
12 G 0.510.1104165
1123217
18 G 0.511.8141236
1123220
25 G 0.513.7224324
1123232
2 X 0.756.34360
1123233
3 G 0.756.65277
1123234
3 X 0.756.65277
1123235
4 G 0.757.16187
1123236
4 X 0.757.16187
1123237
5 G 0.757.972106
1123238
5 X 0.757.972106
1123241
7 G 0.758.589129
1123242
7 X 0.758.589129
1123247
12 G 0.7511.1138211
1123248
12 X 0.7511.1138211
1123251
18 G 0.7513211307
1123254
25 G 0.7515.1280413
1123266
2 X 1.06.65179
1123267
3 G 1.06.96288
1123268
3 X 1.06.96288
1123269
4 G 1.07.474106
1123270
4 X 1.07.474106
1123271
5 G 1.08.388124
1123272
5 X 1.08.388124
1123274
7 G 1.08.9112155
1123275
7 X 1.08.9112155
1123280
12 G 1.011.7185250
1123281
12 X 1.011.7185250
1123284
18 G 1.014.1268368
1123290
25 G 1.016.2354493
1123291
25 X 1.016.2354493
1123306
2 X 1.57.26591
1123307
3 G 1.57.682112
1123308
3 X 1.57.682112
1123309
4 G 1.58.4100141
1123310
4 X 1.58.4100141
1123311
5 G 1.59.1119161
1123312
5 X 1.59.1119161
1123314
7 G 1.510154206
1123315
7 X 1.510154206
1123320
12 G 1.513.4268355
1123324
18 G 1.515.8373517
1123328
25 G 1.518.2530705
1123339
2 X 2.58.696128
1123340
3 G 2.59.1118157
1123342
4 G 2.510147201
1123344
5 G 2.511.1176248
1123346
7 G 2.512253313
1123349
12 G 2.516.3385524
1123359
3 G 4.010.6178231
1123360
4 G 4.011.8248291
1123361
5 G 4.013.3269361
1123362
7 G 4.014.6371468
1123366
3 G 6.012.7240318
1123367
4 G 6.014.2343437
1123368
5 G 6.015.5441510
1123369
7 G 6.017510662
1123372
4 G 10.017.2495685
1123373
5 G 10.019.5592824
1123374
7 G 10.021.48201067
1123377
4 G 16.020.27361036
1123378
5 G 16.022.68951285
1123381
4 G 25.025.111291663
1123382
5 G 25.02814001976
1123385
4 G 35.028.215462052

Benefits

  • Easy handling and installation due to flexible design
  • Space-saving installation due to small cable diameters
  • Certified for maritime applications
  • Note: for the use of AWM (Appliance Wiring Material) cables in industrial machinery (USA) according to NFPA 79: please see the catalogue appendix table T29

Application range

  • Public buildings like airports or railway stations
  • Plant engineering
    Industrial machinery
    Heating and air-conditioning systems
  • Particularly where human and animal life as well as valuable property are exposed to high risk of fire hazards
  • In EMC-sensitive environments
    (electromagnetic compatibility)
  • Considering the temperature range, a temporary outdoor use is possible

Product features

  • Flame-retardant according to IEC 60332-1-2
    (flame spread on a single cable)
  • No flame-propagation according to IEC 60332-3-22 and IEC 60332-3-24 respectively IEC 60332-3-25 (Flame spread on vertical cable or wire bundle)
  • Halogen-free according to IEC 60754-1
    (amount of halogen acid gas)
    Corrosiveness of combustion gases according to IEC 60754-2 (degree of acidity)
  • Low smoke density according to IEC 61034-2

Norm references / Approvals

  • UL AWM style 21217
  • Based on EN 50525-3-11
  • Based on EN 50525-2-51
  • DNV GL certificate no. TAE00002RK

Product Make-up

  • Fine-wire strand made of bare copper wires
  • Core insulation: Halogen-free
  • Cores twisted in layers
  • Halogen-free plastic foil wrapping
  • Tinned-copper braiding
  • Outer sheath: Special halogen-free compound, grey (similar to RAL 7001)

Classification ETIM 5

  • ETIM 5.0 Class-ID: EC000104
  • ETIM 5.0 Class-Description: Control cable

Classification ETIM 6

  • ETIM 6.0 Class-ID: EC000104
  • ETIM 6.0 Class-Description: Control cable

Core identification code

  • Black with white numbers acc. to VDE 0293-334

Conductor stranding

  • Fine wire according to VDE 0295,
    class 5/IEC 60228 class 5

Minimum bending radius

  • Occasional flexing: 20 x outer diameter
  • Fixed installation: 6 x outer diameter

Nominal voltage

  • U0/U: 300/500 V
  • UL: 600 V

Test voltage

  • Core/core: 4000 V
  • Core/screen: 2000 V

Protective conductor

  • G = with GN-YE protective conductor
  • X = without protective conductor

Temperature range

  • Occasional flexing: -25°C to +70°C (UL: +75°C)
  • Fixed installation: -40°C to +80°C (UL: +75°C)

  • Unless specified otherwise, the shown product values are nominal values. Detailed values (e.g. tolerances) are available upon request.
  • Copper price basis: EUR 150/100 kg. Refer to catalogue appendix T17 for the definition and calculation of copper-related surcharges.
  • Please find our standard lengths at: www.lappkabel.de/en/cable-standardlengths
  • Packaging size: coil ≤ 30 kg or ≤ 250 m, otherwise drum
  • Please specify the preferred type of packaging (e.g. 1 x 500 m drum or 5 x 100 m coils).
  • Photographs and graphics are not to scale and do not represent detailed images of the respective products.